EN54-16 fire emergency broadcasting system provides manual operation and timing programming, and gives priority to the former over the latter; supports real-time monitoring of equipment operating status and recording of operating logs. It meets the relevant standard of “EN54-16 Voice Alarm Control and Indicating Equipment”. The broadcasting system can be used for fire emergency broadcasting, daily service broadcasting and background broadcasting; this system is positioned as a small emergency broadcasting system, mainly used in small shopping malls, small office buildings and exhibition halls, etc.
PAVA9500E is an 8-zone expansion amplifier with main/backup switching function in the EN54-16 system, and is designed to be 2U high, with 2 microphone inputs, 4 analog inputs and 1 line output; provides optional amplifier module; supports the total power of up to 500W; holds 8 zone outputs, with the total power of 500W for all zones.
|
Model |
PAVA9500E |
|||
|
Rated Output Power |
≥500W (100V) |
|||
|
Input Sensitivity |
EMC MIC |
——
|
||
|
LINE |
1000mV 10kΩ |
|||
|
Harmonic Distortion |
EMC MIC |
——
|
||
|
LINE |
<1% 1kHz |
|||
|
Frequency Response |
EMC MIC |
——
|
||
|
LINE |
50Hz-18kHz (±3dB) |
|||
|
S/N Ratio |
EMC MIC |
——
|
||
|
LINE |
>80dB (A-weighted) |
|||
|
EMC LINE AUX OUT |
Output Voltage |
1000mV |
||
|
Frequency Range |
80Hz-15kHz (±3dB) |
|||
|
Harmonic Distortion |
<1% 1kHz |
|||
|
System Connection Control Contact Output/Input |
System Fault Relay Output |
Short circuit, no voltage |
||
|
Emergency Mode Relay Output |
Short circuit, no voltage |
|||
|
Fire Reset Input |
Short circuit, t≥0.5S, no voltage |
|||
|
8 Dry Node Outputs |
Short circuit, no voltage |
|||
|
8 Dry Node Inputs |
Short-Circuit Mode |
Short-circuit input, no voltage |
||
|
Level Mode |
3.3V~24V |
|||
|
Voice Message |
Data Format |
——
|
||
|
Storage Type |
——
|
|||
|
Storage Time |
——
|
|||
|
Operating Power |
AC |
AC 230V/50-60Hz |
||
|
DC |
DC 24V/20A |
|||
|
Machine Dimensions(L*W*H) |
483×320×88 |
|||
|
Package Dimensions(L*W*H) |
530×490×145 |
|||
PAVA9500 8 Zones Voice Alarm Fire Evacuation System Host with Main/Backup SwitchingJune 27, 2023EN54-16 fire emergency broadcasting system provides manual operation and timing programming, and gives priority to the former over the latter; supports real-time monitoring of equipment operating stat...view
PAVA8500E 8 Zones Integrated Voice Alarm PA System Extender AmplifierNovember 14, 2018view
PAVA8500 SofewareApril 13, 2021Description:EN54-16 is a Voice Evacuation System which supports timing programming and manual operation, and is manually prioritized; it supports real-time detection of equipment operation status and ...viewwe will contact you within 24 hours.
Method for Distinguishing Digital and All-digital Conference SystemJune 18, 2021Many novices only know the brand to look at the appearance when purchasing a conference system, and then simply look at the function. They think the conference system is very simple, it is nothing mor...view
DSPPA | Professional Sound System for Yongji Sports CenterMay 19, 2022Abstract: DSPPA Professional Sound System has been applied to Yongji Sports Center in Shanxi Province.view